The AVR R450M is an advanced voltage regulator powered by independent auxiliary windings or a PMG, designed for LSA 46.2, 47.2, 49.1 and LSA 50.2 alternators (optionally 42.2, 43.2, 44.2) and adaptable to shunt, AREP or PMG excitation systems. This AVR incorporates the LAM (Load Acceptance Module) function, which reduces voltage and active load as the generator set speed drops, improving load response and minimising frequency variations. Operates efficiently between -20°C and +70°C, withstanding significant vibration and shock. Its voltage regulation is ±0.5%, with a maximum supply of 150V at 50/60 Hz and advanced electronic protection that reduces the excitation current in the event of a short circuit, loss of voltage reference or over-excitation. Voltage sensing is single-phase (R450M) or three-phase (R450T) with selectable ranges of 80-320V or 320-530V, and it has a current-sensing input (S1, S2) for parallel operation.

$ 246.28 246.28 USD Tax Excluded

246.28 Bs Tax Excluded

  • Model
  • Generator Parts
  • Applicable To
  • Weight
  • Dimensions

This combination does not exist.

Terms and Conditions
30-day money-back guarantee
Shipping: 2-3 Business Days

AVR - R450M is the automatic voltage regulator of the generator: it reads the output voltage and corrects the field excitation so the voltage stays stable as the load changes.

A failing AVR shows up before it dies: voltage dips 5–30 V when a large motor starts, lights flicker, or the control panel reboots. When it fails completely the set delivers only residual voltage or trips on overvoltage.

Specifications and compatibility

Applicable to
LEROY SEMER
Dimensions
17 x 9,5 x 13 cm
Weight
2.00 kg

How to verify before ordering

  • Check that the reference printed on the AVR label (for example AS440, MX341, R120) matches exactly; variants differ in sensing range and excitation level.
  • Confirm the excitation input voltage and the generator type it serves. They are not interchangeable across generator makes or speed ranges.
  • Inspect wiring and brushes before replacing the module: a loose connection produces exactly the same symptoms as a burnt AVR.

Frequently asked questions

How do I know the fault is the AVR and not the generator?

Measure output voltage at steady load. If it is low and does not respond to the excitation trim, while windings and rotating diodes are healthy, the AVR is the suspect. A cross-test with a spare AVR confirms it in minutes.

Can the voltage be trimmed after installation?

Yes. Most of these regulators have a voltage and a stability trim pot. Set them at no load to the site nominal voltage, then verify under load before signing off.