AVR - Automatic Voltage Regulator R450
The AVR R450 is a robust voltage regulator offering a voltage regulation of <±1.5% (with 4% engine control). Its sensing input is selectable between 95-132 V CA or 190-264 V CA (single-phase, 50/60 Hz). The maximum power supply is 150 V to 50/60 Hz. It provides an output of up to 90 V CC at 207 V CA, with a continuous current of 4A and an intermittent capability of 10A per second, maintaining a minimum resistance of 15 ohms. In addition, it includes electronic protection that reduces the excitation current to less than 1A after 10 seconds in the event of a short circuit, and allows an external voltage adjustment of ±10%.
AVR - R450 is the automatic voltage regulator of the generator: it reads the output voltage and corrects the field excitation so the voltage stays stable as the load changes.
A failing AVR shows up before it dies: voltage dips 5–30 V when a large motor starts, lights flicker, or the control panel reboots. When it fails completely the set delivers only residual voltage or trips on overvoltage.
Specifications and compatibility
- Applicable to
- LEROY SEMER
- Dimensions
- 17 x 9,5 x 13 cm
- Weight
- 2.00 kg
How to verify before ordering
- Check that the reference printed on the AVR label (for example AS440, MX341, R120) matches exactly; variants differ in sensing range and excitation level.
- Confirm the excitation input voltage and the generator type it serves. They are not interchangeable across generator makes or speed ranges.
- Inspect wiring and brushes before replacing the module: a loose connection produces exactly the same symptoms as a burnt AVR.
Frequently asked questions
How do I know the fault is the AVR and not the generator?
Measure output voltage at steady load. If it is low and does not respond to the excitation trim, while windings and rotating diodes are healthy, the AVR is the suspect. A cross-test with a spare AVR confirms it in minutes.
Can the voltage be trimmed after installation?
Yes. Most of these regulators have a voltage and a stability trim pot. Set them at no load to the site nominal voltage, then verify under load before signing off.
Related parts
- AVR - Automatic Voltage Regulator R449
- AVR - Automatic Voltage Regulator R450T
- AVR - Automatic Voltage Regulator R450M
- AVR - Automatic Voltage Regulator R250
- AVR - Automatic Voltage Regulator SR7
See the spare parts catalogue or request a quotation quoting the equipment reference. Third-party trademarks are cited for identification purposes only.