Skip to Content

AVR - Automatic Voltage Regulator R448

https://www.bochipower.cc/web/image/product.template/3134/image_1920?unique=9b4d277
(0 review)

The AVR R448 is a compatible voltage regulator for Leroy Somer brushless generators from 50-300KW, suitable for alternators of the 5000, 6000 and 7000 series, and can be powered by PMG, AREP or shunt excitation systems. This AVR, which also replaces models such as Leroy Somer R449, R438 and AEM110RE016, as well as Olympian FG Wilson 922-124, offers a voltage regulation of <±0.5% with the engine adjusted to 4%. Its voltage sensing ranges are 95-140V, 170-260V and 340-520V (selectable 50/60Hz), with a three-phase power input of 40-150V AC. The maximum voltage output is 160 V CC to 120 V CA, with a maximum current of 10 A and a maximum current droop of 4% at PF 0.8. It features residual voltage build-up (>5 V CA), external voltage adjustment of ±10%, 6-150V AC auxiliary winding, a response time of 0.3-1 sec. , and a selectable LAM voltage droop rate of 10% or 15%. Designed to operate over a wide temperature range from -40°C to 60°C, it is robust and has adjustment controls for voltage, stability, UFRO, excitation current limit and droop.

$ 142.96 142.96 USD Tax Excluded

142.96 Bs Tax Excluded

  • Model
  • Generator Parts
  • Applicable To
  • Weight
  • Dimensions

This combination does not exist.

Terms and Conditions
30-day money-back guarantee
Shipping: 2-3 Business Days

AVR - R448 is the automatic voltage regulator of the generator: it reads the output voltage and corrects the field excitation so the voltage stays stable as the load changes.

A failing AVR shows up before it dies: voltage dips 5–30 V when a large motor starts, lights flicker, or the control panel reboots. When it fails completely the set delivers only residual voltage or trips on overvoltage.

Specifications and compatibility

Applicable to
LEROY SEMER
Dimensions
17 x 9,5 x 13 cm
Weight
2.00 kg

How to verify before ordering

  • Check that the reference printed on the AVR label (for example AS440, MX341, R120) matches exactly; variants differ in sensing range and excitation level.
  • Confirm the excitation input voltage and the generator type it serves. They are not interchangeable across generator makes or speed ranges.
  • Inspect wiring and brushes before replacing the module: a loose connection produces exactly the same symptoms as a burnt AVR.

Frequently asked questions

How do I know the fault is the AVR and not the generator?

Measure output voltage at steady load. If it is low and does not respond to the excitation trim, while windings and rotating diodes are healthy, the AVR is the suspect. A cross-test with a spare AVR confirms it in minutes.

Can the voltage be trimmed after installation?

Yes. Most of these regulators have a voltage and a stability trim pot. Set them at no load to the site nominal voltage, then verify under load before signing off.

Related parts

See the spare parts catalogue or request a quotation quoting the equipment reference. Third-party trademarks are cited for identification purposes only.

Specifications

Characteristics
Model R448
Applicable To LEROY SEMER
Weight 2,00 kg
Dimensions 17 x 9,5 x 13 cm
Spare Parts
Generator Parts AVR