AVR - Automatic Voltage Regulator R220
The AVR R220 is an analogue voltage regulator with digital control, ideal and economical for small alternators (LSA40 and LSA42.3, under 100kW), especially in backup or continuous applications. Offers voltage regulation of +/- 0.5% in steady state and at constant speed, with a fast response time of 500 ms. Its rated excitation current is 3A (with a maximum of 7A for 10 seconds) and it has a supply/sensing input of 50/ to 85 (139 V60Hz). It is robust, operating from -40°C to +65°C, and includes voltage and stability adjustment, a 8A slow-blow fuse (non-replaceable) for power supply protection, and is configurable for 50Hz or 60Hz. Complies with I.E.C. standards. 60034-1 and U.L. 508 / C.S.A., being easy to configure and reliable.
AVR - R220 is the automatic voltage regulator of the generator: it reads the output voltage and corrects the field excitation so the voltage stays stable as the load changes.
A failing AVR shows up before it dies: voltage dips 5–30 V when a large motor starts, lights flicker, or the control panel reboots. When it fails completely the set delivers only residual voltage or trips on overvoltage.
Specifications and compatibility
- Applicable to
- LEROY SEMER
- Dimensions
- 17 x 6 x 13 cm
- Weight
- 1.00 kg
How to verify before ordering
- Check that the reference printed on the AVR label (for example AS440, MX341, R120) matches exactly; variants differ in sensing range and excitation level.
- Confirm the excitation input voltage and the generator type it serves. They are not interchangeable across generator makes or speed ranges.
- Inspect wiring and brushes before replacing the module: a loose connection produces exactly the same symptoms as a burnt AVR.
Frequently asked questions
How do I know the fault is the AVR and not the generator?
Measure output voltage at steady load. If it is low and does not respond to the excitation trim, while windings and rotating diodes are healthy, the AVR is the suspect. A cross-test with a spare AVR confirms it in minutes.
Can the voltage be trimmed after installation?
Yes. Most of these regulators have a voltage and a stability trim pot. Set them at no load to the site nominal voltage, then verify under load before signing off.
Related parts
- AVR - Automatic Voltage Regulator R120
- AVR - Automatic Voltage Regulator R250
- AVR - Automatic Voltage Regulator MX341
- AVR - Automatic Voltage Regulator MX321
- AVR - Automatic Voltage Regulator R449
See the spare parts catalogue or request a quotation quoting the equipment reference. Third-party trademarks are cited for identification purposes only.
Specifications
| Characteristics | |
|---|---|
| Model | R220 |
| Applicable To | LEROY SEMER |
| Weight | 1,00 kg |
| Dimensions | 17 x 6 x 13 cm |
| Spare Parts | |
|---|---|
| Generator Parts | AVR |