The AVR MX321 (or MX321-A) is a three-phase thyristor-type automatic voltage regulator, ideal for brushless Stamford generators, with excitation derived from a PMG for high interference immunity. It regulates the generator output voltage by compensating for load, speed, temperature and power factor, ensuring safe and reliable control. Its key specifications include a sensing input of 190-264V AC (2 or 3 phases) and a PMG power input of 190-220V AC (3 phases, 3 wires). Offers a maximum output of 120V DC, with 3.7A continuous (6A intermittent for 10 seconds) and a regulation of +/- 0.5% RMS. It features soft start, overvoltage detection and protection, current limiting, internal shutdown for protection, and an external voltage adjustment of +/- 10%. It is robust, with a wide operating temperature range of -40°C to +70°C and a maximum power dissipation of 18 watts.

$ 167.70 167.7 USD Tax Excluded

167.70 Bs Tax Excluded

  • Model
  • Generator Parts
  • Applicable To
  • Weight
  • Dimensions

This combination does not exist.

Terms and Conditions
30-day money-back guarantee
Shipping: 2-3 Business Days

AVR - MX321 belongs to the generator excitation circuit and holds the output voltage within about ±1 % when the load steps up or down.

AVR wear is thermal. It works inside the generator compartment with no ventilation of its own, so it is usually the first module to age on a high-hour set. Keeping one on the shelf avoids a multi-day stop for a low-cost part.

Specifications and compatibility

Applicable to
STAMFORD
Dimensions
17 x 6 x 13 cm
Weight
1.50 kg

How to verify before ordering

  • Check that the reference printed on the AVR label (for example AS440, MX341, R120) matches exactly; variants differ in sensing range and excitation level.
  • Confirm the excitation input voltage and the generator type it serves. They are not interchangeable across generator makes or speed ranges.
  • Inspect wiring and brushes before replacing the module: a loose connection produces exactly the same symptoms as a burnt AVR.

Frequently asked questions

How do I know the fault is the AVR and not the generator?

Measure output voltage at steady load. If it is low and does not respond to the excitation trim, while windings and rotating diodes are healthy, the AVR is the suspect. A cross-test with a spare AVR confirms it in minutes.

Can the voltage be trimmed after installation?

Yes. Most of these regulators have a voltage and a stability trim pot. Set them at no load to the site nominal voltage, then verify under load before signing off.